Why cold stores use so much energy
A cold store is an insulated building with a refrigeration plant that never stops. Heat leaks in all the time, through the walls, roof and floor, every time a door opens, with every pallet that arrives warmer than the store, and from the forklifts, lights, fans and people working inside. The refrigeration plant has to pump all of that heat out again, around the clock, every day of the year. Unlike an office or a factory, there is no night or weekend shutdown.
The colder the store, the harder the job: a refrigeration system needs more electricity to move each unit of heat when the cold side is colder, so a frozen store uses more energy per square metre than a chilled one of the same size and build.
The temperatures cold stores have to hold
- Frozen: quick-frozen food must be kept at -18°C or colder (the quick-frozen foodstuffs rules, with only brief rises allowed during handling and transport).
- Chilled: in England, Wales and Northern Ireland, food that needs to be kept cold must be held at 8°C or below by law, and the Food Standards Agency recommends 5°C or below. Scotland's rules require such food to be kept refrigerated or in a cool place.
Many sites run several chambers at different temperatures, plus chilled loading docks to cut the heat that comes in with each delivery.
Where the electricity goes
- Compressors: the main load, running whenever the plant is removing heat.
- Evaporator and condenser fans: moving air over the cooling coils inside and rejecting heat outside.
- Defrost: ice builds up on the evaporator coils and has to be melted off regularly, which puts heat back into the store.
- Door heaters and underfloor heating: frozen stores heat door frames so seals don't freeze, and heat under the floor so the ground below doesn't freeze and heave.
- Lighting, battery charging for forklifts and handling equipment.
What cold store operators do about it
- Faster doors, strip curtains, air curtains and chilled docks to keep warm, moist air out.
- Better insulated panels and repairs to damaged panels and seals.
- Variable-speed compressors and fans, better controls and smarter defrost.
- Heat recovery: using the heat the plant rejects for hot water or underfloor heating.
- Changing refrigerant: UK F-gas rules are phasing down HFC refrigerants, so many operators are moving to ammonia, CO2 or other low-impact systems when plant is replaced.
- On-site solar on large flat roofs, and shifting load: a well-sealed frozen store holds its temperature for a while, so some operators run plant harder when power is cheaper.
How much electricity a cold store uses per square metre
The benchmark used for Display Energy Certificates gives a "typical" cold storage building 145 kWh of electricity per square metre of floor a year. That's the figure (from CIBSE TM46, the benchmark set behind the government's DEC methodology) on every single-category cold storage certificate in the government's Display Energy Certificate register. Real sites vary a lot either side of it: frozen stores use more than chilled ones, and tall, well-sealed modern buildings use less per square metre than older, busy ones.
So a dedicated cold store with 1,347 m² of floor, the middle size of the dedicated stores in our list with an EPC, would typically use about 195,000 kWh of electricity a year by that benchmark.
Energy data in our cold store list
- Climate Change Agreements: 150 cold stores in our list are run by 67 companies that hold a Climate Change Agreement in the cold storage sector, which gives them a discount on the Climate Change Levy in return for energy-efficiency targets. The file shows each operator's reported 2024 emissions and whether it met its target. These are for all the sites in the operator's agreement, not one site.
- Energy Performance Certificates: 549 cold stores in England and Wales have the EPC rating, floor area, main fuel and date of their building. We link a certificate only when it's clearly the same building, by its location, never by address.
- Estimated electricity use: 324 dedicated cold stores with an EPC floor area have an estimate (floor area × 145 kWh/m²). Processors are left out, because most of their energy goes on the factory, not the store. The estimate is labelled as one everywhere.
Cold stores in our list by EPC rating
| Main fuel on the EPC | Cold stores |
|---|---|
| Grid Supplied Electricity | 245 |
| Natural Gas | 233 |
| Other | 44 |
| Oil | 14 |
| Dual Fuel Appliances (Mineral + Wood) | 6 |
| Biomass | 5 |
| LPG | 2 |
EPC ratings measure the building as designed (fabric, heating, lighting), not the refrigeration plant, so they're a guide to the building, not to how much the store uses.
Who sells to cold stores
Energy suppliers and brokers, refrigeration engineers and plant manufacturers, insulated panel and door contractors, solar and battery installers, energy consultants, controls specialists, insurers and food logistics businesses all target the same few thousand sites. The hard part is finding them: cold stores are often on anonymous industrial estates and trade under names that don't say what they do.
Cold stores in the UK
Our list has 2,220 cold stores approved by the Food Standards Agency and Food Standards Scotland: 1,123 dedicated cold stores, where refrigerated storage is the whole business, and 1,097 food processors with an approved cold store on site. Each row has the address, postcode and coordinates, the approved activities and product sectors, and the operator's Companies House details. See the UK cold store list and cold stores by region.
Approved cold stores by type
- Dedicated cold store1,123
- Processor with cold store1,097
No public register gives metered energy use for individual sites, so we don't publish any: the site-level electricity figure in the file is an estimate from floor area, and the Climate Change Agreement figures are for the operator's whole agreement.
Get the list
Cold store list + quarterly updates
£599 a year
+ VAT (£718.80) a year
- The full UK cold store list now (Excel + CSV)
- 4 quarterly updates over the year
- A changes file each quarter: new, gone and changed cold stores
- Change vs last refresh column in every file
For £150 more than the one-off list you get the next four quarterly editions, each with a changes file. Renews yearly; cancel any time and keep the files you have had.
UK cold store list
£449
+ VAT (£538.80), one-off
- Every UK approved cold store (Excel + CSV)
- Dedicated store or processor, activities and product sectors
- Operator, Companies House number, status and directors
One edition, dated 26 November 2026. No updates.
2,220 cold stores in the current edition. Pay by card through Stripe. Your files are emailed as a zip (Excel and CSV) within 15 minutes between 7am and 10pm; overnight orders arrive by 7:15am. Prices are plus VAT, which is added at checkout. You get a VAT receipt. For business buyers only; licensed for use in your own business.
See real rows in the free sample (directors' names removed).